Search

1 to 10 of 46
Sort by

Blog Entry
Tip #44 - 6-9-2-1

NFPA 101-2012: 19.7.5.7.2* Containers used solely for recycling clean waste or for patient records awaiting destruction shall be permitted to be excluded from the requirements of 19.7.5.7.1 where all the following conditions are met: (1) Each container shall be limited to a maximum capacity of...

Chad Beebe's profile image

Blog Entry
Tip 32 - No Smoking in the Air Handler

NFPA 90A-2012: 6.4.1 Testing. All automatic shutdown devices shall be tested at least annually. Smoke detection control to shut down an air handler must be tested and documented at least annually. The documentation must indicate that the air handler did shut down. #ASHEComplianceTip


Blog Entry
Tip 45: Don’t Miss a Spare

NFPA 70-2011 408.4 (A) Circuit Directory or Circuit Identification. Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all...


Blog Entry
Tip 48 - Can you gauge the accuracy?

NFPA 25-2011: 5.3.2.1 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Make sure you have documents to show that you have either done the testing or replaced the Gauges #ASHEComplianceTip


Blog Entry
Tip #40 - Dusty Heads

NFPA 25-2011: A.5.2.1.1.2(5) In lieu of replacing sprinklers that are loaded with a coating of dust, it is permitted to clean sprinklers with compressed air or by a vacuum provided that the equipment does not touch the sprinkler. Clean dusty sprinklers with compressed air or vacuum - but don't...


Blog Entry
TIp #8 - Dust in the Wind

FGI Guidelines for the Design and Construction of Hospitals and Outpatient Facilities – 2014: 1-2.3.2.3.1 A written plan, referred to as Infection Control Risk Mitigation Recommendations (ICRMR) is required to describe specific measures that will be implemented during construction to limit...


Blog Entry
Tip #27 - We interrupt this test...

6.4.4.1.1.2 The 10-second criterion shall not apply during the monthly testing of an essential electrical system. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm the capability of the life safety and critical branches to comply with...


Blog Entry
Tip #23 - Don’t Stumble Around in the Dark

NFPA 110-2010: 7.3.1 The Level 1 or Level 2 EPS equipment location(s) shall be provided with battery-powered emergency lighting. This requirement shall not apply to units located outdoors in enclosures that do not include walk-in access. Battery-powered emergency lighting must be provided for...


Blog Entry
Tip #41 - Fire Fighter Use Only

NFPA 101-2012: 9.4.6.2 All elevators equipped with fire fighters’ emergency operations in accordance with 9.4.3 shall be subject to a monthly operation with a written record of the findings made and kept on the premises as required byASMEA17.1/CSA B44, Safety Code for Elevators and Escalators. ...


Blog Entry
Tip #18 - hour for hour....

NFPA 99-2010: 5.1.3.3.2* (4) If indoors, they shall be constructed and use interior finishes of noncombustible or limited-combustible materials such that all walls, floors, ceilings, and doors are of a minimum 1-hour fire resistance rating. The 2012 and previous editions of the required a 1...