Skip to main content (Press Enter).
Log in
Skip auxiliary navigation (Press Enter).
Contact Us
Code of Conduct
ASHE Website
Skip main navigation (Press Enter).
Toggle navigation
Content types
Announcements
Blogs
Communities
Discussions
Events
Glossary
Site Content
Libraries
Date range
on this day
between these dates
Posted by
Home
Communities
All Communities
Browse
Discussion Posts
Library Entries
Participate
Help/FAQs
Volunteer
Volunteer with ASHE
Volunteer Opportunities
Blog Viewer
Back to Blog List
Tip #42 - Time to Replace Those Antiques!
By
Jonathan Flannery
posted
08-01-2019 11:14
Options Dropdown
1
Like
Virginia Cole
NFPA 25-2011: 5.3.1 5.3.1.1.1.3* Sprinklers manufactured using fast-response elements that have been in service for 20 years shall be replaced, or representative samples shall be tested and then retested at 10-year intervals. A quick-response sprinkler, residential sprinkler, and early suppression suppression fast-response (ESFR) sprinklers are examples of fast response sprinklers. If your quick response heads were installed prior to 1999 make sure you have documentation of them being tested or replaced. All heads need to be tested or replaced every 50 years.
How do you know if your head is a standard response or a quick response? one of the common indicators will be that a QR head has a much smaller (3mm) bulb.
#ASHEComplianceTip
0 comments
59 views
Permalink
Home
Communities
All Communities
Browse
Discussion Posts
Library Entries
Participate
Help/FAQs
Volunteer
Volunteer with ASHE
Volunteer Opportunities
© 2018 The American Society for Health Care Engineering of the American Hospital Association
Powered by Higher Logic