TIp #18 - hour for hour...

By Chad Beebe posted 01-02-2020 11:29

  
tip-18-hour-for-hour-1.png
NFPA 99-2010: 5.1.3.3.2* (4) If indoors, they shall be constructed and use interior finishes of noncombustible or limited-combustible materials such that all walls, floors, ceilings, and doors are of a minimum 1-hour fire resistance rating. 

The 2012 and previous editions of the required a 1 hour door perhaps just an oversight by the NFPA committee who in later editions reduced the requirement to 45 minutes. Surveyors will likely look for a 60 minute door.

#ASHEComplianceTip