NFPA 80-2010: 19.3.1, 19.4.1, 19.4.1.1, NFPA 105-2010: 6.4.1, 6.5.2 - Fire and smoke dampers, or combination fire/smoke dampers are tested when they are installed, and again 1 year after installation. The test and inspection frequency shall then be every 4 years, with the exception of hospitals, which shall be every 6 years. #ASHEComplianceTip
View All Compliance Tips

1 comment
47 views

Permalink

Comments

12-01-2018 20:23

Brad

If I have mixed occupencies in my Hospital ie. Nursing Home (SNF) and Healthcare. Do I inspect every 4 06 6 years?