408.4 Field Identification Required. (A) Circuit Directory or Circuit Identification. Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be...
NFPA 25-2011: 14.2.1 Except as discussed in 14.2.1.1 and 14.2.1.4 an inspection of piping and branch line conditions shall be conducted every 5 years by opening a flushing connection at the end of one main and by removing a sprinkler toward the end of one branch line for the purpose of...
NFPA 99-2010: 5.1.3.3.2* (4) If indoors, they shall be constructed and use interior finishes of noncombustible or limited-combustible materials such that all walls, floors, ceilings, and doors are of a minimum 1-hour fire resistance rating. The 2012 and previous editions of the required a 1...
NFPA 80-2010: 19.3.1, 19.4.1, 19.4.1.1, NFPA 105-2010: 6.4.1, 6.5.2 Fire and smoke dampers, or combination fire/smoke dampers are tested when they are installed, and again 1 year after installation. The test and inspection frequency shall then be every 4 years, with the exception of hospitals,...
FGI Guidelines for the Design and Construction of Hospitals and Outpatient Facilities – 2014: 1-2.3.2.3.1 A written plan, referred to as Infection Control Risk Mitigation Recommendations (ICRMR) is required to describe specific measures that will be implemented during construction to limit...
NFPA 101-2012: 9.4.6.2 All elevators equipped with fire fighters’ emergency operations in accordance with 9.4.3 shall be subject to a monthly operation with a written record of the findings made and kept on the premises as required byASMEA17.1/CSA B44, Safety Code for Elevators and Escalators. ...
NFPA 25-2011: 5.3.1 5.3.1.1.1.3* Sprinklers manufactured using fast-response elements that have been in service for 20 years shall be replaced, or representative samples shall be tested and then retested at 10-year intervals. A quick-response sprinkler, residential sprinkler, and early...
NFPA 110-2010: 7.3.1 The Level 1 or Level 2 EPS equipment location(s) shall be provided with battery-powered emergency lighting. This requirement shall not apply to units located outdoors in enclosures that do not include walk-in access. Battery-powered emergency lighting must be provided for...
1 Comment - no search term matches found in comments.
NFPA 101-2012: 19.7.5.7.2* Containers used solely for recycling clean waste or for patient records awaiting destruction shall be permitted to be excluded from the requirements of 19.7.5.7.1 where all the following conditions are met: (1) Each container shall be limited to a maximum capacity of...
NFPA 90A-2012: 6.4.1 Testing. All automatic shutdown devices shall be tested at least annually. Smoke detection control to shut down an air handler must be tested and documented at least annually. The documentation must indicate that the air handler did shut down. #ASHEComplianceTip